C-4 Logic Command/Status Words
20-COMM-M Modbus/TCP Adapter User Manual
Publication 20COMM-UM014C-EN-P
Logic Status Word (Phase II Control)
Logic Bits
1514131211109876543210Status Description
x Active 0 = Not Active
1 = Active
x Running 0 = Not Running
1 = Running
xCommand
Direction
0 = Reverse
1 = Forward
x Actual Direction 0 = Reverse
1 = Forward
x Accel 0 = Not Accelerating
1 = Accelerating
x Decel 0 = Not Decelerating
1 = Decelerating
x Jogging 0 = Not Jogging
1 = Jogging
x Fault 0 = No Fault (Par. 323, 324, 325)
1 = Fault
x Alarm 0 = No Alarm (Par. 326, 327, 328)
1 = Alarm
x Flash Mode 0 = Not in Flash Mode
1 = In Flash Mode
x Run Ready 0 = Not Ready to Run (Par. 156)
1 = Ready to Run
x At Limit
(1)
0 = Not At Limit (Par. 304)
1 = At Limit
x Tach Loss Sw 0 = Not Tach Loss Sw
1 = Tach Loss Sw
x At Zero Spd 0 = Not At Zero Speed
1 = At Zero Speed
x At Setpt Spd 0 = Not At Setpoint Speed
1= At Setpoint Speed
x Enable 0 = Not Enabled
1 = Enabled
(1)
See Parameter 304 - [Limit Status] in the PowerFlex 700S drive User Manual for a description of the limit status conditions.