4-8 Using Modbus/TCP Function Codes
20-COMM-M Modbus/TCP Adapter User Manual
Publication 20COMM-UM014C-EN-P
Table 4.H shows the Logic Status register used for reading 16-bit status
fields or multiple decimal values.
Table 4.H Logic Status Register
To view the Feedback, you must read the decimal values of register
addresses 10023 and 10024 (Table 4.I
) using Function Code 03 or 23. For
details about how the Feedback is scaled, refer to page 4-6
.
Table 4.I Feedback Registers
10 9 Local Control Register Address
11 10 12 11 10
12 11 000= Port 0 (TB)
001= Port 1
010= Port 2
011= Port 3
100= Port 4
101= Port 5
110= Port 6
111= No Local
13 12 Reference Register Address
14 13 16 15 14 13
15 14 0000= Ref A Auto (Par. 90)
16 15 0001= Ref B Auto (Par. 93)
0010= Preset 2 Auto
0011= Preset 3 Auto
0100= Preset 4 Auto
0101= Preset 5 Auto
0110= Preset 6 Auto
0111= Preset 7 Auto
1000= Term Blk Manual
1001= DPI 1 Manual
1010= DPI 2 Manual
1011= DPI 3 Manual
1100= DPI 4 Manual
1101= DPI 5 Manual
1110= DPI 6 manual
1111= Jog Ref
Register
Address
Description Values
10021 Logic Status Word 16-bit word. Bit definitions for PowerFlex 70/700 drives are in
Table 4 .G
. For other products, refer to their documentation.
Register
Address
Description Values
10023
(1)
(1)
For a 16-bit Feedback, you must read the complete 32-bit value.
Feedback Lo Bit 0…15 of 32-bit Feedback or the whole 16-bit Feedback
10024 Feedback Hi Bit 16…31 of 32-bit Feedback
Table 4.G Logic Status Registers (to Controller from Drive) (Continued)
Register
Address
Logic Status Bit PowerFlex 70/700 Example
Description Values