Configuring the I/O 4-27
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Create PLC-5 Ladder Logic for the Logic Status, Feedback, and Datalink Out
1. Insert another separate rung.
2. Double-click the rung to display the rung editor.
3. Enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG11:n), and
n is an unused element of the data file chosen for xx (for example, MG11:0
)
4. Press Enter.
5. Insert another separate rung.
6. Double-click the rung to display the rung editor.
7. Enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ER BND OTU
MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element
(for example, MG11
:0) for the message created in steps 1…4.
Important:The information must be entered with appropriate numbers
for ‘xx’ and ‘n’ for your application, and with spaces and
forward slashes exactly as shown.
8. Press Enter.
9. In the MSG instruction (Figure 4.8
), double-click Setup Screen to
launch the message configuration screen (Figure 4.9
).
Figure 4.8 PLC-5 Ladder Logic for the Logic Status, Feedback, and Datalink
Out
10. Configure the General tab fields by entering or verifying the
information shown in the message configuration screen.
Steps 1…4
Steps 5…8
Step 9