Using the I/O 5-21
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
PLC-5, SLC 500, or
MicroLogix 1100/1400
Controller Example
Drive and Adapter Parameter Settings
The following drive and adapter settings were used for the example ladder
logic program in this section.
Device Parameter Value Description
PowerFlex 70 EC
Drive
90 - [Speed Ref A Sel] 22 (DPI Port 5) Assigns 20-COMM-E to be used for the Reference.
300 - [Data In A1] 140 Points to Par. 140 - [Accel Time 1]
301 - [Data In A2] 142 Points to Par. 142 - [Decel Time 1]
302 - [Data In B1] 100 Points to Par. 100 - [Jog Speed]
303 - [Data In B2] 155 Points to Par. 155 - [Stop Mode A]
304 - [Data In C1] 101 Points to Par. 101 - [Preset Speed 1]
305 - [Data In C2] 102 Points to Par. 102 - [Preset Speed 2]
306 - [Data In D1] 103 Points to Par. 103 - [Preset Speed 3]
307 - [Data In D2] 104 Points to Par. 104 - [Preset Speed 4]
310 - [Data Out A1] 140 Points to Par. 140 - [Accel Time 1]
311 - [Data Out A2] 142 Points to Par. 142 - [Decel Time 1]
312 - [Data Out B1] 100 Points to Par. 100 - [Jog Speed]
313 - [Data Out B2] 155 Points to Par. 155 - [Stop Mode A]
314 - [Data Out C1] 101 Points to Par. 101 - [Preset Speed 1]
315 - [Data Out C2] 102 Points to Par. 102 - [Preset Speed 2]
316 - [Data Out D1] 103 Points to Par. 103 - [Preset Speed 3]
317 - [Data Out D2] 104 Points to Par. 104 - [Preset Speed 4]
PowerFlex
750-Series
Drive
(1)
545 - [Spd Ref A Sel] Port 0: Port 6 Reference Assigns 20-COMM-E to be used for the Reference.
895 - [Data In A1] Port 0: Accel Time 1 Points to Par. 535 in the drive.
896 - [Data In A2] Port 0: Testpoint Sel 1 Points to Par. 970 in the drive.
897 - [Data In B1] Port 5: Anlg Out1 Hi Points to Par. 90 in Port 5 (I/O module).
905 - [Data Out A1] Port 0: DC Bus Volts Points to Par. 11 in the drive.
906 - [Data Out A2] Port 0: Open Loop Fdbk Points to Par. 137 in the drive.
907 - [Data Out B1] Port 5: Anlg Out0 Data Points to Par. 77 in Port 5 (I/O module).
20-COMM-E
Adapter
04 - [IP Addr Cfg 1]
07 - [IP Addr Cfg 4]
10.91.100.79 IP address for the adapter.
08 - [Subnet Cfg 1]
11 - [Subnet Cfg 4]
255.255.248.0 Subnet mask for the adapter.
23 - [DPI I/O Cfg] xxx1 1111 Enables Cmd/Ref and Datalinks A…D.
35 - [M-S Input] xxx1 1111 Configures the I/O Data to be transferred from the
controller on the network to the drive.
36 - [M-S Output] xxx1 1111 Configures the I/O Data to be transferred from the
drive to the controller on the network.
(1)
In this example, the 20-COMM-E adapter/20-750-20COMM Communication Carrier Card is installed in Port 6, and a 24V I/O module is installed
in Port 5. Also, Data In B2…D2 (Parameters 898…902) and Data Out B2…D2 (Parameters 908…912) are enabled, but not used.
TIP: Data In parameters are inputs into the drive that come from controller
outputs (for example, data to write to a drive parameter). Data Out
parameters are outputs from the drive that go to controller inputs (for
example, data to read a drive parameter).