Ethernet-to-DeviceNet Linking Device 39
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
42 1 USINT
Scrolling Device Address
and Status
The scrolling address and status fields
scroll through the address and status
of all DeviceNet slaves that are
faulted. This scrolling includes the
linking device scanner itself.
If there are no faulted nodes, both the
scrolling address and status are set to
0.
The scrolling fields change once a
second.
43 1 USINT
44 20 USINT[20] N/A
64 64 USINT[64] Device Status The current status of each DeviceNet
slave node. Each array element is the
status of the node at the
corresponding MAC ID.
If a node is not configured in the
linking device scan list, the status
value will be set to 0.
The linking device scanner status
appears at the entry associated with
the linking device MAC ID.
Status Assembly Format (cont.)
Byte
Offset
Size in
Bytes
Data
Type
Name (RSLogix 5000
software version 13
or later)
Description