Wire the Relay Cartridge
1. Detach the 4-pin clamp-style removable connector from the relay
cartridge and connect wiring as shown below:
,PSRUWDQW The required wire diameter specification for the relay
cartridge is 12-22 AWG. The wire must be solid,
stranded or fine stranded copper. The maximum length
between the connector and power source/relay must
be less than 10 meters (unless all circuit components,
modules and the power source are located within the
same NEMA enclosure).
,PSRUWDQW As shown in the wiring diagram below, you must
install both of the following:
an external FLM, slo-blo 0.5A fuse in series with the L1 line
connecting to the 4-pin ARI connector, and
a surge suppressor (such as Allen-Bradley cat. nos. 700-N5 or -
N24) across the external 700P relay coil
2. Reattach the wired connector to the relay cartridge.
4-pin removable
connector
FLM 0.500A fuse
(customer-installed)
L1
120V
AC
N
(L2)
Surge supressor
(customer-installed)
700P Relay