Rockwell-automation 1771-OFE/B Analog Output Module User Manual Manuel d'utilisateur Page 60

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 84
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 59
MAX
6-8
Publication 1771Ć6.5.30 - November 1998
Figure 6.6
Location of Resistor Pots
TP1
TP2
TP3
TP
4
TP
5
TP
6
T
P7
T
P8
T
P9
TP10
TP12
Resistor Potentiometers
Adjustment Screws
Configuration Jumpers
(set for +
10V scale)
LAST STATE
12993
R67 R66
R73R74
R81 R80
R88 R87
Channel 0
Channel 1
Channel 2
Channel 3
12.Output full scale (+20mA) again, either with write block transfer
data or by placing the LAST STATE configuration jumpers in the
MAX position.
13.Adjust R66 until the reading is 5V +
2mV.
14.Reconnect the voltmeter to the appropriate screws on the field
wiring arm. Repeat Steps 8 through 13 for Channels 2, 3, and 4
until the desired tolerance is obtained. Table 6.C lists the
appropriate resistor pots.
Table 6.C
Resistor Pots
Channel Resistor Pots
1 R66, R67
2 R73, R74
3 R80, R81
4 R87, R88