0100
Channel 3 Minimum Scaling Factor Polarity
Set (1) = Negative
Reset (0) = Positive
Binary
BCD
12892
4-6
Publication 1771Ć6.5.30 - November 1998
Figure 4.3
Binary Configuration Word Represented in BCD
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Word 5 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0
Block transfer operation with the PLC-3 processor uses one binary
file in a data table section for module location and other related data.
This is the block transfer control file. The block transfer data file
stores data that you want transferred to your module (during block
transfer write) or from your module (block transfer read). The
address of the block transfer data file is stored in the block transfer
control file. A sample program segment is shown in Figure 4.4 and
described in the following paragraphs.
The industrial terminal prompts you to create a control file when
either block transfer instruction is entered. The same block transfer
control file is used for both read and write instructions for your
module.
PLC-3 Example Program
Module Location Rack 1, Module Group 0, Slot 1
Block Transfer Control File FB1:0
BTW File (Configuration file) FB2:1
BTR File (Buffer file) FB3:1
Output Data File FB4:1
Storage Bit B0/0
BTW Done Bit B1:0/05
BTR Done Bit B1:0/15
Module Configuration 1771ĆOFE1 (Voltage Version)
Voltage Range 1to5V
Data Format BCD
Scaling Parameters
Channels 1 and2=Noscaling
Channel 3 = Ć20 to 275
Channel 4 = 100 to 500
Block Transfer
Programming Ć PLCĆ3
Family Processors Only