MAX
MIN
MAX
6-4
Publication 1771Ć6.5.30 - November 1998
Figure 6.3
Location of Configuration Jumpers and Resistor Pots
TP1
TP2
TP3
TP
4
TP
5
TP
6
T
P7
T
P8
T
P9
TP10
TP12
Resistor Potentiometers
Adjustment Screws
Configuration Jumpers
(set for +
10V scale)
LAST STATE
12993
R67 R66
R73R74
R81 R80
R88 R87
Channel 0
Channel 1
Channel 2
Channel 3
8. Place the processor in the TEST or PROG mode.
9. Output full scale (+10V) either with write block transfer data or
by placing the LAST STATE configuration jumpers in the MAX
position.
10.Adjust R66 until the reading is 10V +
1mV.
11. Output -10V either with write block transfer data or by placing
the LAST STATE configuration jumpers in the MIN position.
12.Adjust R67 until the reading is one-half the difference between
-10V and the initial reading.
13.Output full scale (+10V) again, either with write block transfer
data or by placing the LAST STATE configuration jumpers in the
MAX position.
14.Adjust R66 again until the reading is 10V +
1mV.