Rockwell-automation 1771-N SERIES High Resolution Analog Module User M Manuel d'utilisateur Page 87

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 188
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 86
Specifications A–7
Publication 1771ĆUM127B-EN-P - December 2002
Figure A.2
Derating Curves for 50mA Outputs on the 1771ĆN Series Modules
0102030405060
0
10
20
30
40
50
Ambient Temperature (
o
C)
Output Current vs. Ambient Temperature
as a function of Load Resistance
Output
Current
(mA)
Important: If you require 60
o
C operation with 50mA outputs, install a
resistance in series with the load impedance so that the total load
impedance is equal to 300 ohms.
Vue de la page 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 187 188

Commentaires sur ces manuels

Pas de commentaire