
Specifications A–7
Publication 1771ĆUM127B-EN-P - December 2002
Figure A.2
Derating Curves for 50mA Outputs on the 1771ĆN Series Modules
0102030405060
0
10
20
30
40
50
Ambient Temperature (
o
C)
Output Current vs. Ambient Temperature
as a function of Load Resistance
Output
Current
(mA)
Important: If you require 60
o
C operation with 50mA outputs, install a
resistance in series with the load impedance so that the total load
impedance is equal to 300 ohms.
Commentaires sur ces manuels