Rockwell-automation 1771-N SERIES High Resolution Analog Module User M Manuel d'utilisateur Page 153

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 188
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 152
Appendix I
Publication 1771ĆUM127B-EN-P - December 2002
Block Transfer Write and Block
Transfer Read Configurations
for 6 Output/2 Input 1771ĆN
Series Modules
This appendix contains block transfer write and block transfer read
configurations and bit/word descriptions for 1771-N series modules
with six outputs and two inputs.
Block Transfer Write Configuration Block for 6 Output/2 Input
Modules
Word/Dec. Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
BTW word type Constant Number of outputs Constant
010 0 0 1 0 0 0 0 1 1 0 0 0 0 0
1 Channel 1 Output Data
2 Channel 2 Output Data
3 Channel 3 Output Data
4 Channel 4 Output Data
5 Channel 5 Output Data
6 Channel 6 Output Data
7 Unused = 0
BCD
select
Temp
scale
Verify
8 RTS Sample Time: 1 millisecond units
Channel 1 Programming
9 Low Scale Value
10 High Scale Value
11 Low Clamp Value
12 High Clamp Value
13
Alarm
enable
Reset State 0 Maximum Ramp Rate, % of Full Scale per second
14 Reset Value
What This Appendix
Contains
Vue de la page 152
1 2 ... 148 149 150 151 152 153 154 155 156 157 158 ... 187 188

Commentaires sur ces manuels

Pas de commentaire