4–14 Configuring the Module
Publication 1771ĆUM127B-EN-P - December 2002
Figure 4.7
Digital Filter Lag Equation Illustration
100%
63%
0 0.01 0.5 0.99 Time in Seconds
1
TA = 0.99 sec
TA = 0.5 sec
TA = 0.01 sec
Unfiltered Input
0
Amplitude
Thermocouple Type
This field lets you select the type of sensor connected to a
thermocouple input channel. This field must be 0 for all other
channel types.
Sensor Type Binary Value
Decimal 15 14 13 12
Octal 17 16 15 14
Millivolt 0 0 0 0
B 0 0 0 1
E 0 0 1 0
J 0 0 1 1
K 0 1 0 0
R 0 1 0 1
S 0 1 1 0
T 0 1 1 1
C
1
1 0 0 0
N
1
1 0 0 1
1
For 1771ĆNT2 only.
Commentaires sur ces manuels