Application Examples
Entering Negative Position Data
The position data is sign magnitude. There are three ways to easily
assign a negative number:
Using the ladder
Manipulating the bits manually
Calculating manually
To enter negative position data using the ladder:
1. Divide the absolute value into most (MSW) and least significant
(LSW) words.
2. Use bitwise “inclusive or” with MSW and 32768.
3. Place the result in the position MSW, LSW.