48 Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
4. Choose Download.
The Download dialog opens with a reminder of the following.
The controller is in Remote Run mode.
The mode changes to Remote Program prior to download.
5. From the Download dialog, choose Download
The RSLogix 5000 software dialog opens.
6. Notice that the 1756-ENBT Bridge is now online.
If yellow triangles are present, see the following section.
Verify the Module Chassis
Size
You have now built the I/O tree in the RSLogix 5000 software, and the
RSLogix 5000 software used the chassis size from the 1734-AENTR General tab.
Now you need to download this new chassis size value into the 1734-AENTR
adapter hardware. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the 1734-AENTR adapter hardware.
1. Verify that the RSLogix 5000 software is online.
2. In the Project dialog, right-click the 1734-AENTR adapter under I/O
Configuration.