Rockwell Automation Publication 1734-UM017B-EN-P - October 2013 29
Chapter
4
Configure the Adapter for Direct Connection
in RSLogix 5000 Software
Overview
In this example, a ControlLogix controller communicates with I/O modules via
the adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by the
data. The modules presented in this chapter use RSLogix 5000 software,
revision 17 and above.
Topic Page
Set Up the Hardware 30
Create the Example Application 31
Configure the I/O Modules 32
Add the Local EtherNet/IP Bridge to the I/O Configuration 33
Add the POINT I/O Adapter to the I/O Configuration 36
Add the POINT I/O Modules to the I/O Configuration 40
Edit the Controller Tags 46
Create the Ladder Program 47
Download the Program to the Controller 47
Verify the Module Chassis Size 48
Configure the Adapter with Fixed IP Address 51
Recover From an Overloaded Adapter 52
ATTENTION: You must only use Series C and above POINT I/O modules
with 1734-AENTR EtherNet/IP Adapters. Series A or Series B POINT I/O
modules do not work with 1734-AENTR EtherNet/IP Adapters (does not
apply to POINTGuard modules).