Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-17
9. Verify your screen appears as shown below.
On the Subnet, the 1738-ADNX is a scanner and it is always at
node 0. It is OK for some or all of the node numbers on the
Subnet to be the same as devices on the primary network.
Because they are two different networks, duplicate node errors
will not occur. The 1738-ADNX will communicate back to the
1756-DNB scanner as a single entity (only taking up one node
number on the main network).
To view the configuration you just created, upload the scanlist
from the 1738-ADNX.
10. Double click on the 1738-ADNX to bring up its properties page.
11. Select the Scanlist tab and when prompted select Upload.
The nodes can be in any order. Verify:
All four are there
They have the correct node numbers
Make sure
you click
Upload! You
do not want t
o
download
over the
configuration
you just
created.