Publication 1738-UM001A-EN-P - February 2005
Default Data Maps D-9
1738-OE2C Analog Current Output Module
Message size: 4 bytes
Message size: 2 Bytes
1738-OE2V Analog Output Module
Message size: 2 Bytes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Consumes (Tx) Output Channel 0 High Byte Output Channel 0 Low Byte
Output Channel 1 High Byte Output Channel 1 Low Byte
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Produces (Rx) High Byte - Channel 1 Status Low Byte - Channel 0 Status
Not used HCA LCA CM CF Not used HCA LCA CM CF
Where: CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LCA = Low Clamp Alarm; 0 = no error, 1 = fault
HCA = High Clamp Alarm; 0 = no error, 1 = fault
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Produces (scanner Rx) Channel 1 Status - High Byte Channel 0 Status - Low Byte
Not used HCA LCA CM ST Not used HCA LCA CM ST
Where: ST = Channel Fault Status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LCA = Low Clamp Alarm; 0 = no error, 1 = fault
HCA = High Clamp Alarm; 0 = no error, 1 = fault