D-6 Default Data Maps
1738-OV4E Protected Sink Output Module
Message size: 1 Byte
Message size: 1 Byte
1738-OW4 Relay Sink/Source Output Module
Message size: 1 Byte
76543210
Produces (scanner Rx) Not used Ch3 Ch2 Ch1 Ch0 Channel status
Where: Ch0 = output channel 0, Ch1 = output channel 1, Ch2 = output channel 2, Ch3 = output channel 3; 0 = no error 1 = error
76543210
Consumes (scanner Tx) Not used
Ch3 Ch2
Ch1 Ch0 Channel state
Where: Ch0 = output channel 0, Ch1 = output channel 1, Ch2 = output channel 2, Ch3 = output channel 3; 0 = OFF 1 = ON
76543210
Consumes (scanner Tx) Not used
Ch3 Ch2
Ch1 Ch0 Channel state
Where: Ch0 = output channel 0, Ch1 = output channel 1, Ch2 = output channel 2, Ch3 = output channel 3; 0 = OFF 1 = ON