Planning Your System Programs
Chapter 6
6-8
Table 6.E
Data
T
able Memory Usage
File Type
File Type
Identifier
File
Number
Memory Used in Over
head for Each File
(16bit words)
Memory Used
(16bit words) per
Word, Float Word,
Character, or Structure
Output Image O 0 2 1/word
Input Image I 1 2 1/word
Status S 2 2 1/word
Bit (binary) B 3 2 1/word
Timer T 4
1
2 3/structure
Counter C 5
1
2 3/structure
Control R 6
1
2 3/structure
Integer N 7
1
2 1/word
FloatingPoint F 8
1
2 2/float word
ASCII A 3999 2
1
/
2
per character
BCD D 3999 2 1/word
Undefined  9999 2 0
1
This
is the default file number
. For this file type, you can assign any file number from 3 thru 999.
Data table files are contiguous in memory. Size in words for I/O files
0 and 1 are:
For this processor: Files O0 and I1 memory size:
PLC5/10, 5/12, 5/15 Is fixed at 32 words
PLC5/25 Varies from 3264 words (32 is the default)
Status file 2 is fixed at 32 words for each processor. Files 3-999 vary in
size. These files contain only the number of words corresponding to the
highest address that you assign. Each B, N, A, and D file can be 1,000
words maximum. Each F file can be 1,000 float words (32-bit words)
maximum. Each T, C, R, and SC file can be 1,000 structures maximum.