Selecting Switch Settings
Appendix A
A-9
Set SW2 switch assembly switches for an adapter-mode PLC-5 processor
in a PLC-2/20 or -2/30 processor system or sub I/O scanner module
system. Set switches 2 through 8 for the number of words communicated
from host processor to adapter processor, for the I/O group, and for the
rack number of the I/O group of the adapter processor, respectively.
Switch 1 is unused.
12345678
1234
Bottom View of Module
Switch Assembly SW2
Switch Assembly SW3
toggle pushed
on (closed)
toggle pushed
off (open)
Side View
toward bottom
toward top
If you want: Set switch: To:
Switch 1 is always unused. 1 off
The host processor to use 8 words to communicate with the adapter PLC5 2 off
The host processor to use 4 words to communicate with the adapter PLC5 2 on
First I/O group to be 0 3 on
First I/O group to be 4 3 off
Select the I/O rack number of the adapter PLC5 processor 4 through 8 see below
Rack 4 5 6 7 8
01 on on on on on
02 on on on on off
03 on on on off on
04 on on on off off
05 on on off on on
06 on on off on off
07 on on off off on
AdapterMode
ProcessorsSW2
in a
PLC2/20, 2/30, or Sub I/O
Scanner Module System