204 SCR Diagnostic Register (Continued)
Bit: 10
Hex Value: 0400H
Sug. Var. Name:
SCR_15@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
SCR 15 Fault (Reverse Bridge)
Blt:
11
Hex Value: 0800H
Sug. Var. Name:
SCR_16@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
SCR 16 Fault (Reverse Bridge)
205/1 205 Interlock Register
Interlock tests are executed whenever bits O-7 of register 100/1 100 are set. The first problem
detected will be indicated by the corresponding bit in this register. These bits will remain latched until
a Warning Reset is issued by the setting and clearing of bit 9 of register 100/1 100. Note that these
bits will prevent the CML or FML from running. Refer to the DPS SD3000 Diagnostics,
Troubleshooting, and Startup Guidelines Instruction Manual (S-301 1) for more information about the
interlock tests.
Bit: 0
Hex Value:
0001 H
Sug. Var. Name:
WCI_ILL@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description: The More Than One CML Request bit is set when more than one incompatible CML
operating mode is requested at a time in register 100/1 100. The following operating modes are
mutually exclusive:
l Armature Alpha Test
l Armature Identification Test
l CML Run.
This bit is also set if the CML is turned on when the UDC task is not running. This bit is also set if you
have attempted to restart the drive without resetting the appropriate command bits from register
100/1 100. Recall that the bits in register 100/1 100 are edge-sensitive. See Appendix G for additional
information.
Bit:
1
Hex Value: 0002H
Sug. Var. Name:
WCI_CNF@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The CML Parameters Are Not Loaded bit is set if the armature configuration parameters
have not been downloaded into the UDC module from the Programming Executive.
3-33