Rockwell-automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Manuel d'utilisateur Page 28

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 168
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 27
4-4
DeviceNet Adapter for use with DPI AC Drives
4.3.2 Going Online with RSNetWorx for DeviceNet
You can view the devices on a DeviceNet network by going online. A
device may appear as an unrecognized device (node 63 in figure
4.3) if RSNetWorx for DeviceNet does not have an Electronic Data
Sheet (EDS) file for it. See table 4.3 for the procedure to view
devices.
Table 4.3 – Viewing Devices on the DeviceNet Network using RSNetWorx
Step Action Icon
1. After setting up a driver in RSLinx, start
RSNetWorx for DeviceNet.
2. Select
Network > Online
. If the Browse
for Network dialog box appears, RSLinx
has multiple drivers configured. Select
your DeviceNet network, and click
OK
. A
prompt appears.
3. Click
OK
to go online. The devices on the
network appear in the Configuration View.
You can select Graph, Spreadsheet, or
Master/Slave views. Figure 4.3 shows a
sample network in a Graph view.
Shortcut to
RSNetWorx
Figure 4.3 – Sample DeviceNet Network (Graph View)