48 Developing an HMI Application
Analog Alarm
The standard configuration uses four thresholds, defined as follows.
An alarm is not clearable until the device in alarm is back in a normal state.
The analog alarm value H123\H456\H78\Val\PVA stays at the alarm level,
until it has been acknowledged by the operator with the display acknowledge
button
. An analog alarm counts as 1 alarm, even if two messages are visible in
the alarm list (for example, High-alarm and Max-alarm).
Threshold
Severity Alarm Label Direction
H123\H456\H78\Set\NV 1 H123-H456.H78:NA Decreasing
H123\H456\H78\Set\LV 2 H123-H456.H78:LA Decreasing
H123\H456\H78\Set\HV 2 H123-H456.H78:HA Increasing
H123\H456\H78\Set\MV 1 H123-H456.H78:MA Increasing