76 Publication 2711P-QS001A-EN-P - October 2007
Chapter 6 Review Unsupported Features and Implement Workarounds for Migration Issues
14. Add a numeric display to
the display and set the
Value connection to the
same tag in step 8.
The numeric display helps
the operator to identify the
set bit cursor points.
15. Add an interlock push
button to the display, assign
the tag in step 7 to the Value
connection, and set the
button value to 1.
The operator can enable the
ActiveX control by clicking
the interlock push button,
setting the Select connection
value to 1.
16. Add another interlock push
button to the display, assign
the tag in step 7 to the Value
connection, and set the
button value to 0.
The operator can disable
the ActiveX control by
clicking the interlock push
button, setting the Select
connection value to 0.
Provide Visual Feedback
1. Select
Objects>Indicators>Symbol.
2. Draw a box on the display.
Vue de la page 75