Chapter 14
Entering DTAM Configuration Data
1415
Advisor Update Rate
When selecting Advisor Update Rate from the SLC 500 Configuration -
Option Selection menu, the following is displayed:
The Advisor Update Rate is the periodic rate at which the DTAM scans the
Advisor register. For example a rate of 2.00 means the DTAM reads the
advisor register once every 2 seconds.
To assign a new Advisor Update Rate, enter a valid decimal number and
press [Return]. The valid range is from 1 to 12.5 seconds. The default is 2
seconds. Entries are rounded up to the next higher 0.1 second.
Note: Because the advisor adds to the communications traffic, the rate
should be set to the highest possible value.
To save the new Advisor Update Rate, press [Esc]. You are returned to the
SLC 500 Configuration - Option Selection menu.