Operations 3-3
Error Mode
In error mode (LED turns red), the RediSTATION monitors the error
state for correct operation. Errors are critical or noncritical.
See the troubleshooting chart on page 4-2 for details on how to
recover from an error.
Resetting the Device
To reset the RediSTATION, you must cycle power to the unit or briefly
disconnect the DeviceNet connector.
Error Type Description LED State
Critical
(Not recoverable)
Failure of diagnostic tests during
powerup/reset mode
Solid Red
Over-temperature condition of
outputs during runtime
Changes to DIP switches during
runtime
Duplicate node address detected
Incorrect data rate
Non-critical
(Recoverable)
Pilot lamp burned out Flashing Red
Pilot lamp wired incorrectly
I/O connection timeout