1 Publication 2705-UM001A-EN-P
Chapter
3
Operations
Chapter Objectives
This chapter contains the following sections:
Modes of Operation
The RediSTATION has 4 modes of operations: Powerup / Reset Mode,
Idle Mode, Run Mode, and Error Mode.
Powerup/Reset Mode
During a powerup or reset, the RediSTATION:
1. Clears outputs (turns outputs off) and cycles the LED indicator
through solid red, green and off. The LED remains off until the
test is completed.
2. Performs powerup diagnostic tests including:
- EPROM checksum test
- RAM read/write test
- Watchdog timer test
- Serial number verification
If any test fails, the outputs remain off and the LED shows solid
red. You must cycle power to recover from a powerup
diagnostic test failure. Repeated failures indicate a faulty unit.
3. Reads and stores the DIP switch settings.
Important: Changes to DIP switch settings are allowed only in
powerup or reset mode. Changes to DIP switch settings under
power cause an error.
Section Page
Modes of Operations 3-1
Resetting the Device 3-3
DeviceNet Operations 3-4