Publication 1794-UM065B-EN-E - September 2010
20 Install Your FLEX I/O Analog Modules
2. Drill the necessary holes for the #6 self-tapping mounting screws.
3. Mount the mounting plate for the adapter module using two #6
self-tapping screws (18 included for mounting up to 8 modules and the
adapter).
4. Hold the adapter at a slight angle and engage the top of the mounting
plate in the indention on the rear of the adapter module.
5. Press the adapter down flush with the panel until the locking lever locks.
6. Position the terminal base unit up against the adapter and push the
female bus connector into the adapter.
7. Secure to the wall with two #6 self-tapping screws.
8. Repeat for each remaining terminal base unit.
ATTENTION
Be careful of metal chips when drilling cable mounting holes.
Do not drill holes above a system that has any modules installed.
IMPORTANT
Make certain that the mounting plate is properly grounded to
the panel. Refer to Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
.