Additional HART Protocol Information 111
61 Read dynamic
variables and PV
analog output
None 0 PV analog output units
code
1…4 PV analog output level (F)
5 PV units code
6…9 Primary variable (F)
10 SV units code
11…14 Secondary variable (F)
15 TV units code
16…19 Third variable (F)
20 FV units code
21…24 Fourth variable (F)
62 Read analog outputs 0 Analog output number
code for slot 0
0 Slot 0 analog output
number code
1 Slot 0 units code
2…5 Slot 0 level (F)
1 Analog output number
code for slot 1
6 Slot 1 analog output
number code
7 Slot 1 units code
8…11 Slot 1 level (F)
2 Analog output number
code for slot 2
12 Slot 2 analog output
number code
13 Slot 2 units code
14…17 Slot 2 level (F)
3 Analog output number
for slot 3
18 Slot 3 analog output
number code
19 Slot 3 units code
20…23 Slot 3 level (F)
Common Practice Commands
Command Data in Command Data in Reply
# Function Byte Data
Type
(5)
Byte Data
Type
(5)
Vue de la page 122