Rockwell-automation 1794-IJ2XT FLEX I/O Frequency Input Modules User M Manuel d'utilisateur Page 35

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 87
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 34
Publication 1794-6.5.11 - September 2011
Install Your FLEX I/O Frequency Input Module 25
Resolution % is defined as:
Accuracy % is defined as:
% Resolution =
100
Count frequency x minimum frequency sample time
% Accuracy =
100
1 -
Minimum frequency sample time
2
Minimum
frequency sample
time
1
count frequency
+
Resolution and Accuracy
Accuracy
Minimum
Frequency
Sample
Time (ms)
Sampling
Accuracy
Time
Base
Accuracy
Worst
Case
Total
Accuracy
Deviation in Hz Due to
Total Accuracy
Resolution
1.0…3276.7
Frequency
Range
(in Hz)
1…32767
Frequency
Range
(in Hz)
2 0.02% 0.0225% 0.0425 0.1…1.4 1…14 0.01%
4 0.01% 0.0225% 0.0325 0.1…1.1 1…11 0.005%
5 0.008% 0.0225% 0.0305 0.1…1.0 1…10 0.004%
10 0.004% 0.0225% 0.0265 0.1…0.9 1…9 0.002%
20 0.002% 0.0225% 0.0245 0.1…0.8 1…8 0.001%
50 0.0008% 0.0225% 0.0233 0.1…0.8 1…8 0.0004%
100 0.0004% 0.0225% 0.0229 0.1…0.8 1…8 0.0002%
200 0.0002% 0.0225% 0.0227 0.1…0.7 1…7 0.0001%
500 0.00008% 0.0225% 0.02258 0.1…0.7 1…7 0.00004%
1000 0.00004% 0.0225% 0.02254 0.1…0.7 1…7 0.00002%
Input Map
Bit 15141312111009080706050403020100
Word Read
0 Frequency 0…32,767 or 0.0…3,276.7 Channel 0
1 % Full Scale 0.0…3,276.7% Channel 0 or Acceleration -32,768…32,767 Channel 0
2 Frequency 0…32,767 or 0.0…3,276.7 Channel 1
3 % Full Scale 0.0…3,276.7% Channel 1 or Acceleration -32,768…32,767 Channel 1
4 R R Direction
Ch 0
GS
Ch 0
F/A
Ch 0
WO
Ch 0
MPA
Ch 0
R R Direction
Ch 1
GS
Ch 1
F/A
Ch 1
WO
Ch 1
MPA
Ch 1
Vue de la page 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 86 87

Commentaires sur ces manuels

Pas de commentaire