6 CompactBlock Distributed I/O on Remote I/O Series D
Publication
1791R-IN002B-EN-P - August 2003
Set the Node Address on the Base Module
The node address for network connection is set using two 8-bit DIP switches.
To set the node address, lift the door containing the status LEDs on the top
left side of the module. The switches are read at module power up only. The
rack address setting and the starting quarter setting are described below.
IMPORTANT
It is important to monitor the rack fault bit. When
installing a system for the first time, it is possible to
mistakenly put devices with duplicate rack addresses
on the same network. Blocks with duplicate addresses
may in certain instances cause outputs to toggle on/off
until the duplicate address error is corrected.
1
2
ON
3
4
5
6
7
8
1
2
ON
3
4
5
6
7
8
View when looking into module
43313
SW2 SW1