Rockwell Automation Publication 1788-UM059A-EN-P - August 2014 23
Configure the Linking Device Chapter 3
Enable/Disable Autobaud
Autobaud is disabled by default. You can turn it on or off by following the
procedure below.
1. In RSNetWorx for DeviceNet software, click the linking device icon.
2. From the Device pull-down menu, choose Class Instance.
3. If a warning dialog box appears, click Yes.
The Class Instance Editor dialog box appears.
4. From the Description pull-down menu, choose Set Single Attribute.
5. Choose the appropriate options in the Class Instance Editor dialog box.
In This Box Choose
Object Address
Class
Instance
Attribute
3
1
64h
Data Sent to Device 00 to enable Autobaud
01 to disable Autobaud
Transmit Data Size Byte
IMPORTANT
Make sure the Values in Decimal checkbox is cleared.