10 PLC-5 Ethernet Interface Module
Publication 1785-IN019B-EN-P - January 2007
If you want to send an email to a specific recipient when a controller application
generates an alarm or reaches a certain condition, program the controller to send the
message instruction to the destination of the email.
2. Verify the rung.
3. Click Setup Screen.
A dialog appears like the one below.
The three Data fields display the string values of the ST file element addresses.
4. Enter the appropriate information into the Data fields and Username and Password,
if Authentication is enabled, to send email.
Examine the Error Code (denoted in Hex) and Error Description areas within the
General tab to see if the message was successfully delivered.
Error Code (hex) Description
0x000 Delivery successful to the mail relay server.
0x002 Resource unavailable. The email object was unable to obtain memory
resources to initiate the SMTP session.
0x101 SMTP mail server IP address not configured.
0x102 To (destination) address not configured or invalid.
0x103 From (reply) address not configured or invalid.
0x104 Unable to connect to SMTP mail server.