Rockwell Automation Publication 1769-UM012B-EN-P - January 2014 87
Appendix A
Configure the 1769-ASCII Module as a Generic
Module
This example demonstrates a CompactLogix program using channel 0 of the
ASCII module to collect a line of input from HyperTerminal and echo that line
back to you.
For information on the MicroLogix controller, see Configure the Module for Use
with a MicroLogix Controller on page 57.
Use the following quick start to make sure your ASCII module is functioning
properly.
1. Open Logix Designer software.
2. Create a new project.
In this example, the name of the project is L35 CR_Quickstart_001.
3. Create a 1769-MODULE (generic) in the I/O configuration.
4. When the I/O module properties appear, enter the following information:
a name, the appropriate slot number, specify a Comm Format of
Data_INT, and enter the following values:
5. Press OK.
Assembly Instance Size
Input 101 108
Output 100 108
Configuration 102 31