Publication ENET-UM527E-EN-P - October 2006
36 Configure a Network Address For a Web Server Module
Use the Rockwell Automation BOOTP/DHCP Utility
The module ships with DHCP enabled. The BOOTP/DHCP utility is a
stand alone program that lets you interactively define the IP address of
a module that is issuing DHCP or BOOTP requests. The utility is
located in the:
BOOTP-DHCP Server folder in the Rockwell Software program
folder on the Start menu.
The utility is automatically installed when you install
RSLinx software.
Tools directory on the RSLogix 5000 installation CD.
To use the BOOTP/DHCP utility:
1. Launch the BOOTP/DHCP software.
In the Request History panel you see the hardware addresses of
modules issuing requests.
2. Double-click on the hardware (MAC) address of the module you
want to configure.
IMPORTANT
Before you start the BOOTP/DHCP utility, make sure you have the
hardware (MAC) address of the web server module. The hardware
address is on a sticker located on the side of the module. The
hardware address in a format similar to: 00-0b-db-14-55-35.