150 Socket Interface
MSG Destination Element
Create a user-defined data type.
where:
Considerations
See Programming Considerations on page 135 for more information.
Element Element Description
FromAddr structure A user-defined structure that contains the address to read.
Family INT Contains the address family. Must be 2.
Port INT Contains a local port number.
Addr DINT Contains an IP address.
BufLen DINT Contains the number of bytes of data received.