D-4 RSFieldbus Time Stamping Setup
3. Test the time stamping.
a. Place a transmitter's RESOURCES block in and out of service;
AUTO to OOS to AUTO.
b. The TIME_STAMP sub-parameter for the BLOCK_ALM
parameter should have a time stamp of when the RESOURCE block
went to OOS.
c. The TIME_STAMP sub-parameter for the UPDATE_EVT
parameter should have a time stamp of when the RESOURCE block
went to AUTO.