Rockwell-automation 1757-FFLD Linking Device Configuration Manual Manuel d'utilisateur Page 101

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 150
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 100
Publication 1757-PM002A-EN-E - June 2006
Applications 4-47
Ratio PID Logic
Block Block Type Parameter Element Value
CON FLOW Analog
Input
MODE_BLK TARGET Auto
XD_SCALE (these
values must match
the
PRIMARY_VALUE_
RANGE of the
transducer block)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL 1
L_TYPE Direct
PID PID MODE_BLK TARGET CAS
GAIN Loop
Dependent
RESET
RATE
PV_SCALE (these
values must match
in Analog Input
range)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
UNC FLOW Analog
Output
MODE_BLK TARGET Auto
XD_SCALE (these
values must match
the
PRIMARY_VALUE_
RANGE of the
transducer block)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL 1
L_TYPE Direct
RATIO Arithmetic MODE_BLK TARGET Auto
ARITH_TYPE Traditional
summer
GAIN ratio
IN_1 STATUS GNC
IN_2 STATUS GNC
IN_3 STATUS GNC
Vue de la page 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 ... 149 150

Commentaires sur ces manuels

Pas de commentaire