Publication 1746-UM026A-EN-P - September 2003
4-20 Configuring the Module
]/[
I:1.8
2
OTHER
] [
I:1.8
1
OTHER
0001
MOV
MOVE
Source 10000
10000
Dest O:1.24
10000
<
<
CH0_PARAMETER2
MOV
MOVE
Source 5905
5905
Dest 0:1.8
4113
<
<
CH0_CONFIG
MOV
MOVE
Source 5000
5000
Dest O:1.16
5000
<
<
CH0_PARAMETER1CH0_CLAMPING_SET CH0_LIMIT_AL_SET
The rung below configures Channel 0 for 0 to 21 mA, sets the alarm limit range from 5000 to 10000, and holds the output in its last state on a fault
condition.
Note: 5905 decimal = 0001 0111 0001 0001 binary.
]/[
I:1.8
2
OTHER
] [
(END)
I:1.8
1
OTHER
0002
0003
MOV
MOVE
Source 4113
4113
Dest O:1.8
4113
<
<
CH0_CONFIGCH0_CLAMPING_SET CH0_LIMIT_AL_SET
I:1.8/2 --> CH0_LIMIT_AL_SET
The rung below configures Channel 0 for 0 to 21 mA, sets the parameter option to “no action”, and holds the output in its last state on a fault
condition. Note: 4113 decimal = 0001 0000 0001 0001 binary.