8–5
Application Examples
Publication
17466.8 - April 1997
Channel Configuration
Configuration setup for current transducers:
• channels 0, 1, and 2
• 4–20 mA input type
• engineering units data format
• zero data word in the event of an open circuit
• 10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection
Configuration setup for pressure transducer:
• channel 3
• 4–20 mA input type
• engineering units data format
• zero data word in the event of an open circuit
• 10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection
Configuration setup for level sensor:
• channel 4
• 0–10V dc input type
• engineering units data format
• zero data word in the event of an open circuit
• 10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection