Chapter 6
Publication
17466.8 - April 1997
Ladder Logic Configuration
Examples
Earlier chapters explained how the configuration word defines the
way a channel operates. This chapter shows the programming
required to enter the configuration word into the processor memory.
It also provides you with segments of ladder logic specific to unique
situations that might apply to your programming requirements. The
example segments include:
initial programming of the configuration word
interfacing the analog module to a PID instruction
monitoring channel status bits (Class 3 Mode only)
To enter data into the channel configuration word (O:e.0 through
O:e.7) when the channel is disabled (bit 11 = 0), follow these steps.
Refer to page 5–2 for specific configuration details.
Example - A 1746-NI8 analog module is residing in slot 3 of a 1746
chassis. Configure all eight channels with the same parameters.
Input Type:
4-20 mA
Data Format:
scaledforPID
Open Circuit:
zero if open circuit
Filter Frequency:
10 Hz
Channel Enable:
enabled
Not Used
Bit Setting
1112131415
0000
910 8 67450123
Bit Number
1100 00110100
This example transfers configuration data and sets the channel enable
bits of all eight channels with a single File Copy instruction.
Initial Programming