Rockwell-automation T7420A_AF ICS Regent+Plus Analog Input Modules 60H Manuel d'utilisateur Page 23

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 29
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 22
Analog Input Modules
(T7420A, AF)
PD
-
7023
Mar
-
06
23
Figure
14
. I/O Extender Connections for Differential Analog Input Calibration.
Within each pair of jumper posts, make sure that you connect
the voltage source to the jumper posts nearest the front of the
I/O extender. Do not make any connections to the jumper
posts nearest the I/O chassis backplane
these connect to the
actual field wiring attached to the I/O slot terminals on the I/O
chassis.
Calibration Steps
1.
Remove the module to be calibrated from the I/O chassis.
2.
Install the I/O extender module into the slot from which
the module was removed.
3.
Remove the jumpers (if installed) labeled CH1 through
CH16 from the I/O extender module.
Important!
Vue de la page 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 29

Commentaires sur ces manuels

Pas de commentaire