Rockwell-automation T7411F ICS Regent+Plus Monitored Digital input Mod Manuel d'utilisateur Page 11

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 24
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 10
Monitored Digital Input Modules
, Type F (T7411F, T7418F)
PD
-
7027
Mar
-
06
11
Line
Monitoring
For DC powered inputs, the monitored digital input module
can perform line monitoring of the field wiring when a
suitable line monitor device is installed across the field input
switch. A variety of line monitor devices are available to
match the voltage and input redundancy used in the
application.
Figure
6
shows a single switch connected to a single monitored
input module. This type of configuration uses a line monitor
device which contains two resistors, one in ser
ies with the field
switch and one in parallel with the field switch. Figure
6
also
applies to fault tolerant input configurations that include
redundant sensors connected to redundant input modules.
Figure
6
. Line Monitoring, Single Switch Connected to
Single Module.