Publication 900-UM004D-EN-E - July 2010
Communications Data 3-9
C3 (83) 003E Transfer output type H’00000000 (0): OFF
H’00000001 (1): Set point
H’00000002 (2): Set point during SP ramp
H’00000003 (3): PV
H’00000004 (4): MV monitor (heating)
H’00000005 (5): MV monitor (cooling)
Initial
setting
C3 (83) 003F Transfer output upper
limit
H’FFFFF831…H'0000270F (−1999…9999) ➑
C3 (83) 0040 Transfer output lower
limit
H’FFFFF831…H'0000270F (−1999…9999) ➑
C3 (83) 0041 Linear current output H’00000000 (0): 4…20 mA
H’00000001 (1): 0…20 mA
C3 (83) 0042 Input shift type H’00000000 (0): Temperature input 1-point shift
H’00000001 (1): Temperature input 2-point shift
Advanced
function
setting
C3 (83) 0043 MV at stop and error
addition
H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 0044 Auto/manual select
addition
H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 0045 RT H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 0046 HS alarm use H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 0047 HS alarm latch H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 0048 HS alarm hysteresis H’00000001…H’000001F4 (0.1…50.0)
C3 (83) 0049 LBA detection time H’00000000…0000270F (0…9999)
C3 (83) 004A LBA function group H’00000001…0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
C3 (83) 004B LBA band H’00000000…0000270F
(0.0…999.9 for TC/Pt multi-input models)
(0.00…99.99 for Analog input models)
C3 (83) 004C Protocol Setting ➌ H’00000000 (0): CompoWay/F (900-TC)
H’00000001 (1): Modbus
Communi
cations
setting
C3 (83) 004D Send data wait
time➌
H’00000000…H’00000063 (0…99)
Table 3.3 Variable Type C3 (83)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function
Group
➊ The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.
➋ The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.
➌ Communications parameters are enabled after they have been changed by resetting the controller.
➍ For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2
➎ For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.
➏ PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
➐ The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.
➑ The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
➒ P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
➓ The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.