Publication 900-UM004D-EN-E - July 2010
Communications Data 3-5
Table 3.3 Variable Type C3 (83)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function
Group
C3 (83) 0000 Input Type (TC/Pt
multi-input models)
H’00000000 (0): Pt (200…850°C/300…1500°F)
H’00000001 (1): Pt (199.9…500.0°C/199.9…900.0°F)
H’00000002 (2): Pt (0.0…100.0°C/0.0…210.0°F)
H’00000003 (3): JPt (199.9…500.0°C/199.9…900.0°F)
H’00000004 (4): JPt (0.0…100.0°C/0.0…210.0°F)
H’00000005 (5): K (200…1300°C/300…2300°F)
H’00000006 (6): K (20.0…500.0°C/0.0…900.0°F)
H’00000007 (7): J (100…850°C/100…1500°F)
H’00000008 (8): J (20.0…400.0°C/0.0…750.0°F)
H’00000009 (9): T (200…400°C/300…700°F)
H’0000000A (10): T (199.9…400.0°C/199.9…700.0°F)
H’0000000B (11): E (0…600°C/0…1100°F)
H’0000000C (12): L (100…850°C/100…1500°F)
H’0000000D (13): U (200…400°C/300…700°F)
H’0000000E (14): U (199.9…400.0°C/199.9…700.0°F)
H’0000000F (15): N (200…1300°C/
300…2300°F)
H’00000010 (16): R (0…1700°C/0…3000°F)
H’00000011 (17): S (0…1700°C/0…3000°F)
H’00000012 (18): B (100…1800°C/300…3200°F)
H’00000013 (19): Infrared temperature sensor (K 140°F/60°C)
H’00000014 (20):Infrared temperature sensor (K 240°F/120°C)
H’00000015 (21):Infrared temperature sensor (K 280°F/140°C)
H’00000016 (22): Infrared temperature sensor (K 440°F/220°C)
H’00000017 (23): 0…50 mV
H’00000018 (24): W (0... 2300°C/0...3200°F)
H’00000019 (25): PL II (0... 1300°C/0...2300°F)
Initial
setting
Input Type (analog
input models)
H’00000000 (0): 4…20 mA
H’00000001 (1): 0…20 mA
H’00000002 (2): 1…5 V
H’00000003 (3): 0…5 V
H’00000004 (4): 0…10 V
C3 (83) 0001 Scaling Upper Limit Scaling lower limit +1…0000270F (scaling lower limit +1…9999)
C3 (83) 0002 Scaling Lower Limit H’FFFFF831 to Scaling upper limit -1 (-1999 to scaling upper limit
-1)
C3 (83) 0003 Decimal Point
Position (TC/Pt
multi-input models)
H’00000000…H’00000001 (0…1)
Decimal Point
Position (analog input
models)
H’00000000…H’00000003 (0…3)
C3 (83) 0004 Temperature Unit H’00000000(0): °C
H’00000001(1): °F
C3 (83) 0005 SP Upper Limit The range of values (without decimal point) is as follows:
Temperature: SP lower limit + 1 to Input range upper limit
Analog: SP lower limit + 1 to Scaling upper limit
C3 (83) 0006 SP Lower Limit The range of values (without decimal point) is as follows:
Temperature: Input range lower limit to SP upper limit - 1
Analog: Scaling lower limit to SP upper limit - 1
C3 (83) 0007 PID/ ON/OFF H’00000000(0) ON/OFF
H’00000001(1) 2-PID Control
C3 (83) 0008 Standard/Heating
and Cooling
H’00000000(0): Standard
H’00000001 (1) Heating and cooling
The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.
The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.
Communications parameters are enabled after they have been changed by resetting the controller.
For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2
For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.
PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.
The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.