Rockwell-automation 5720 DriveLogix System Manuel d'utilisateur Page 98

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 263
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 97
Publication 20D-UM002C-EN-P - November 2003
4-14 Placing and Configuring Local I/O
where:
This address variable: Is:
Location Identifies network location
LOCAL = local DIN rail or chassis
ADAPTER_NAME = identifies remote adapter or bridge
SlotNumber Slot number of I/O module in its chassis
Type Type of data
I = input
O = output
C = configuration
S = status
MemberName Specific data from the I/O module; depends on the type of
data the module can store
For example, Data and Fault are possible fields of data for an
I/O module. Data is the common name for values the are sent
to or received from I/O points.
SubMemberName Specific data related to a MemberName.
Bit (optional) Specific point on the I/O module; depends on the size of the
I/O module (0-31 for a 32-point module)
Vue de la page 97
1 2 ... 93 94 95 96 97 98 99 100 101 102 103 ... 262 263

Commentaires sur ces manuels