Publication 2098-RM003A-EN-P October 2001
Command Reference 2-63
Motor Intermittent Current
Motor Continuous Current
Format: :aa039fddddcc<cr>
Parameter
Code:
0x039
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dddd Motor intermittent current rating, in units of
Amps*128.
Minimum
Value:
0x0001
Maximum
Value:
0x7FFF
Default: 2560
Format: :aa03Afddddcc<cr>
Parameter
Code:
0x03A
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dddd Motor continuous current rating, in units of
Amps*128.
Minimum
Value:
0x0001
Maximum
Value:
0x7FFF
Default: 640