Configuring the Interbus Scanner 4-13
16. Repeat steps #14 and #15 using the 2.0 PCP icon . Enter a
Station name such as “PowerFlex 70 Demo #2”. Note the
Communication Reference (CR) is 3. The CR needs to be known
when using PCP communication services (explicit messaging). Click
OK when complete.
17. When complete, the representation area will look as shown in Figure
4.15.
Figure 4.15 Example PowerFlex 70 Demo #2
18. Right-click on the SST-IBS-SLC icon and select P
arameterization/
Execute. Select “Startup without PDP” as shown in Figure 4.16 and
click OK. This uses the mapping already set up in the scanner and
does not allow re-mapping by the software tool.
20COMM-UM007A-EN-P.book Page 13 Tuesday, January 22, 2002 10:52 AM