DeviceNet Serial Interface Module 17
Publication 1799-IN012B-EN-P - July 2008
Parameter # Access Description Parameter Choices Default
Setting
Default
Value
Data
Type
Gateway Consume on DeviceNet Network from Master
Consume
string data
type
22 Get/Set Defines the
format of the
data string
received from the
master.
0 = Array
1 = Short string
2 = String
Short
string
1USINT
Transmit
Swap mode
23 Get/Set If enabled, the
position of the
bytes in the serial
messages is
swapped every 2
or 4 bytes.
0 = Disabled
1 = 16-bit Swap
Enabled
2 = 24-bit Swap
Enabled
3 = 32-bit Swap
Enabled
Disabled 0 USINT
Gateway
consume
assembly
size
24 Get Total number of
I/O data bytes
that are received
from the master.
This should be
the TX size of
your scanner.
4…254 20 bytes
of array
data and
4 header
bytes
24 USINT
Parameter # Access Description Parameter
Choices
Default
Setting
Default
Value
Data
Type
Serial Port Transmit/Explicit Messages from EDS Editor
Transmit
data string
25 Get/Set Serial data to be
sent to the serial
transmit buffer.
ASCII block data Empty USINT
Transmit
data length
26 Get/Set Length of the
Transmit Serial
Data.
0…250 0 0 USINT
Vue de la page 16