E-4 Configure the 1797-IE8H Module in RSLogix 5000 Software Over the ControlNet Network
Filter Cutoff
The generic profile sets all of the filter bits to 0, which is an invalid value. You
must set these bits to a valid value or you will get a diagnostic error value of 2.
Channel Bits
0…3 [Adapter Name]:[Slot]:C.Data[0].5
[Adapter Name]:[Slot]:C.Data[0].6
[Adapter Name]:[Slot]:C.Data[0].7
4…7 [Adapter Name]:[Slot]:C.Data[1].5
[Adapter Name]:[Slot]:C.Data[1].6
[Adapter Name]:[Slot]:C.Data[1].7
Filter Cutoff Bits Description
765
000Not Valid
001Not Valid
010Not Valid
0 1 1 10 Hz (100 ms)
1004 Hz (250 ms)
1012 Hz (500 ms)
1101 Hz (1 s)
1110.5 Hz (2 s)